Condensation on a VELUX, and reading the weather it happens in

Water on a roof window is reported as a leak more often than as anything else, and most of the time nothing is leaking. The single most useful diagnostic is not where the water is. It is what the weather was doing.

The rule in one line

Rain leaks follow rain. Condensation follows cold. Driving rain leaks follow wind.

Three causes, three weather signatures, and between them they account for almost everything.

The weather table

Reading water on a roof window by the weather it appears in
Weather Cause Where the water is A fault?
Cold night, dry, often clear Room condensation on the glass Inside face of the pane Usually not
Cold and clear, no rain Cold bridge at the frame or reveal Frame and plaster reveal Yes
Clear still night, spring or autumn Dew on a well insulated unit Outside face of the pane No. The opposite
Any weather, never clears Failed edge seal Between the panes Yes, and terminal
Heavy rain, any wind Flashing or covering failure Head or sides, following rain Yes
Driving rain, one wind direction Missing underlay collar Head of the window Yes

Everything below expands a row of that table.

Start with the question nobody asks

The first question is not what the water is. It is what the weather was doing when it appeared, and almost nobody notices because the water is what they are looking at.

So the first thing worth doing costs nothing: for the next fortnight, note the date each time it happens and what the weather was. Cold and dry. Cold and clear. Mild and raining. Windy from the south west. Four or five entries settle the diagnosis.

The physics of each cause is set out in full on the lantern condensation page, which covers the four surfaces water appears on and why. This page is about the sequence for working out which one you have, and about the things specific to a roof window in a loft.

Why a loft room is worse than the rest of the house

Warm moist air rises, and in a house it collects at the top. A loft room is therefore the most humid room in the building before anybody does anything in it.

Add a bedroom, where two people breathing overnight put a surprising quantity of water into a closed room, and a loft bathroom or en suite next door, and the humidity in a loft is genuinely higher than downstairs.

That is why roof windows mist when the windows downstairs do not, and it is the reason the answer is usually ventilation rather than glazing.

The inside of a trussed rafter roof space, W shaped webs and punched metal plate joints clearly visible at the intersections, daylight from a gable vent
The insulation collar, and the age it dates from

The insulation collar, and the age it dates from

Water on the frame and running down the plaster reveal, on cold clear nights, is the one fault on this list that belongs specifically to how roof windows used to be fitted.

An insulation collar carries the insulation up to the frame so the reveal is not a cold bridge. It became normal practice comparatively recently, which means a rough rule applies: on a roof window fitted more than about twenty years ago, assume there is not one, and on a window that runs with water every January, assume it with some confidence.

It is why an old roof window gets written off as a cold, wet thing that was never going to be anything else. It was not the window.

Which loft rooms get it worst

Within one house, the roof windows that mist are predictable, and the pattern is worth knowing before assuming a particular unit is faulty.

  • The loft bathroom or en suite. Highest humidity in the house, in the highest room, frequently with the weakest extract.
  • A bedroom with the door kept shut. Two people overnight in a closed room with no air exchange.
  • A window on a north facing slope. Never gets sun on it, so the glass stays cold for longer each morning.
  • A window behind a closed blackout blind. Still air against the glass, covered below.
  • A window with its trickle vent shut. No background ventilation at all, covered below.

Where one window in a house mists and another does not, the difference is almost always in that list rather than in the units.

Comparing the windows you have

A house with more than one roof window has a built-in control experiment, and it is worth using before anybody quotes for anything.

If every roof window in the house mists on the same night, the driver is the house: humidity, heating pattern, ventilation. If one mists and the others do not, the driver is that room or that window, and the list above narrows it in a minute.

If one has misting between the panes and the rest are clear, that is a failed seal on one unit and nothing to do with the house at all.

The trickle vent, and why it is closed

Most roof windows have a ventilation flap or trickle vent in the top of the sash, providing background ventilation with the window shut.

It is closed on a great many of the windows we look at, usually because somebody felt a draught in January and shut it, and it was never reopened. The room then has no background ventilation at all, and the humidity climbs.

Opening it is free and it is the first thing to try on a misting window. On an older unit the flap sometimes seizes, which is a small service item rather than a reason to leave it shut.

Ventilation, in the order that works

  1. Extract at source: a bathroom fan and a cooker hood that vent outside rather than recirculating.
  2. Background ventilation: the trickle vent open, all year.
  3. Purge: opening the window fully for a few minutes after a shower or overnight moisture, which clears a room far faster than leaving it ajar for hours.
  4. Not drying laundry in the room, which is the single largest avoidable source in most houses.

Removing vapour at source beats removing it from the room, and both beat trying to warm every surface it might land on.

Marine grade stainless steel fixings and a coated aluminium frame section laid out on a roof membrane before installation, salt haze in the air
The loft hatch, and the draught you cannot see

The loft hatch, and the draught you cannot see

In a house with a converted loft the roof windows are the visible part of a system, and there is an invisible part that frequently matters more.

Where the conversion is partial, or where a section of unconverted roof space adjoins the room, the junction between warm room and cold void is where moisture goes. An uninsulated, unsealed hatch or access panel into that void lets warm humid air straight into a cold space, and it condenses there rather than on the window.

That does not cause the misting on the glass, and it does mean the room is losing moist air into a place it should not be. When we are up in a loft anyway it is worth looking at, and it is frequently the cheapest improvement available in the whole house.

The window is the coldest thing in the room, by design

It is worth stating plainly, because it changes how people read the symptom.

Even an excellent modern rooflight loses heat faster per square metre than the insulated roof around it. That is not a defect; glass is glass. It means the glass will always be the coldest large surface in a loft room, and therefore the first surface any excess humidity finds.

A window that mists is therefore doing what a thermometer does. It is telling you the humidity in that room is higher than the surface temperature can carry, and the useful response is to ask why the humidity is that high rather than to ask what is wrong with the glass.

What a dehumidifier will and will not do

People reach for one, and it is worth being straight about what it achieves.

A dehumidifier removes moisture from the air in the room it is in, so it does reduce condensation on the glass in that room while it is running. It is genuinely effective in a loft bedroom on cold nights.

What it does not do is remove the source. It is treating the symptom continuously and at a running cost, where an extract fan ducted outside removes the vapour at the moment it is generated for far less. Where somebody is running a dehumidifier in a loft every winter, the honest advice is to look at the extract and the trickle vents first.

Timber frames, and the reason it matters

Older roof windows are timber framed with a lacquered or painted internal finish, and that finish is what protects the timber from the room.

Where condensation has been running down the frame every winter for years, and the finish was never renewed, the bottom of the sash is where the decay starts. It is the corner that also carries the most ironmongery.

A polyurethane coated unit needs nothing internally and is the obvious specification for a loft bathroom or any room where humidity is high. On a replacement it is worth specifying rather than matching what was there.

A single roof window fitted into a concrete interlocking tile roof on a post war house, the deep profile flashing dressed carefully over the roll of each tile
Where the water goes once it forms

Where the water goes once it forms

Condensation on a roof window does not stay where it forms, and that is why the position of a stain is poor evidence.

Water on the inside of the glass runs down to the bottom of the sash, where most windows have a small channel and a drainage path to take it away. Where that channel is blocked with dust, or where the volume exceeds it, the water goes over the edge onto the reveal below, and from there onto the plaster and eventually the floor.

So a puddle on a windowsill or a stain at the bottom of a reveal frequently originates as mist on the glass a metre above it. Clearing the sash channel is a two minute job and it is worth doing before concluding anything.

Blinds, and the trap in them

A blackout blind in side channels is very good at excluding light, and it also holds a layer of still air against the glass.

That layer is not ventilated, so on a cold night the glass behind a closed blackout blind runs colder than glass with the room air moving across it, and it collects more condensation rather than less. People then find water behind the blind in the morning and conclude the window has failed.

It has not. The remedy is to open the blind during the day so the glass and the fabric both dry, and to deal with the room humidity, which is the actual driver. It is not a reason to avoid blackout blinds in a loft bedroom, where they are frequently essential.

The four questions we ask first

Before anybody goes on the roof, four answers separate every cause on this page, and all four can be given from indoors.

  • Which surface is the water on: inside the glass, outside the glass, between the panes, or on the frame?
  • What was the weather doing: raining, windy, cold and clear, or mild?
  • Does it clear, and how fast?
  • Is it all round the opening, or at one corner?

When it is worth calling somebody

Most condensation on a roof window needs a change to ventilation rather than a visit. It is worth calling when misting has appeared between the panes, when water runs off the frame and reveal every cold night, when staining or mould has started on the plaster, or when water appears in rain from one wind direction.

The first and second are the window and the installation. The third means it has been going on long enough to be doing damage. The fourth is not condensation at all.

The question we start with on a VELUX

We ask which surface, what weather, and whether it clears, before quoting anything, because three of the causes are not fixed by replacing the unit. Where it is a failed seal we replace the unit. Where it is the frame and reveal we fit an insulation collar, which means opening up and is the only real fix. Where it is the room we say so plainly rather than selling a window nobody needs.

The weather is the diagnosis. The position of the water only narrows it down.

Thinking about this job? We survey across Worthing, West Sussex and the South Downs and give you a fixed price before any work starts, with a 10-year workmanship guarantee.

Get a fixed quote

Get a fixed quote

Tell us about the roof. We will tell you the price.

A survey costs you nothing and there is no obligation attached to it. We look at the roof build-up, the exposure and the opening, and give you one fixed figure, not an estimate that moves once work starts.

If your rooflight is leaking now, say so and we will prioritise the survey.

  • Fixed price, confirmed in writing
  • 10-year workmanship guarantee
  • Installed to current Building Regulations
  • Your roof is never left open overnight
Call Get a fixed quote