A correctly installed roof window does not leak. When one does, the cause is almost always the flashing kit not matching the covering profile, an underlay collar left cut or dressed the wrong way, or covering reinstated badly around the opening. All three are installation faults specific to a unit set into a pitched covering.
How to tell a leak from condensation
The diagnostic method is the same for every rooflight and it is set out on do flat roof rooflights leak.
In short: water during rain is ingress, water on cold mornings is condensation, and which side of the glass it is on separates a failed unit from a room problem.
What follows is what is specific to a pitched installation.
The wrong kit for the profile
The commonest cause on a pitched roof by a wide margin.
A flat profile kit fitted to a deeply profiled concrete tile leaves an open void under every roll, running the full height of the window on both sides.
What the kit families are is on what is a flashing kit.
Why it survives ordinary rain
Because gravity is doing most of the work.
Water running down a slope passes the voids without entering them. It is wind driving water across and up the slope that pushes it under the rolls.
Which is why the fault appears in a particular wind direction, seasons after the installation.
The underlay collar
The second cause, and it is entirely hidden.
Beneath the covering there is a membrane carrying away whatever gets past, and the collar has to take that membrane around the frame and discharge it onto the covering below the window.
Cut and left, or dressed so water runs behind rather than over, there is no second line at all.
Which way the collar laps
A detail that is right or completely wrong, with nothing in between.
The collar overlaps the membrane above the window and is overlapped by the membrane below it, so water runs over each junction rather than into it.
Reversed, it channels water straight into the roof space.

The covering reinstatement
The third cause, and it is workmanship rather than specification.
Tiles or slates cut to fit around a frame, reinstated with inadequate lap, or broken and left in place, admit water the kit was never asked to manage.
On slate the reinstatement around an opening is most of the skill in the job.
Soakers not interleaved
A specific version of the same fault.
Side soakers are woven between the courses so each is overlapped by the covering above it. Laid on top of the tiles rather than between them, they collect water instead of shedding it.
From the ground the two look identical.
Water above the window
Where a pitched installation differs from a flat one.
A roof window has the whole slope above it draining down onto its head flashing, which a flat roof unit does not, so anything upslope matters.
A valley, a chimney or another window discharging above one is a real consideration in positioning.
Snow, and where it sits
A seasonal cause specific to a slope.
Snow accumulates against the head flashing of a window on a shallow pitch and melts slowly from the roof side, producing water sitting where the detail assumes it runs away.
It is another argument for respecting the minimum pitch.
Below the minimum pitch
The cause that is designed in rather than built in.
A unit fitted below its stated pitch does not shed water reliably, and the failure is outside warranty.
The figures are on the minimum pitch for a roof window.
The sash gasket
The one failure that is genuinely the window.
A perished gasket on an opening sash shows as water at one edge in driven rain, and it is a serviceable part rather than a reason to replace the unit.

Reusing an old kit
The false economy that causes a new window to leak.
Soakers work in the covering over years and the underlay collar perishes, so a new window on an old kit fails at the detail nobody replaced.
A replacement includes a new kit as a matter of course.
What a stain some distance away means
That the entry point is not where the water appears.
Water entering at a head flashing runs down a rafter and appears at a ceiling well below the window, which is why the stain is a poor guide.
Why replacing the window rarely helps
Because it addresses none of the three causes.
A new unit with the old kit, into the same covering, on the same pitch, will do exactly what the old one did.
Battens cut short at the opening
A workmanship fault specific to a pitched roof and it is invisible afterwards.
Tiling battens either side of an opening have to bear properly on the trimmers, and where they are cut short and left unsupported the covering above the window sags over time.
A sagging course above a window is what breaks the head flashing detail years later.
Working on the roof afterwards
A cause of leaks that has nothing to do with the original installation.
Somebody servicing an aerial, a satellite dish or a chimney who walks the covering around a window can displace a soaker or crack a tile without noticing.
Where a window has been sound for years and then leaks, it is worth asking what else has been done on that roof.
What we order
We order the kit against the measured covering profile, fit the underlay collar as part of the installation, and reinstate the covering with proper laps rather than patching around the frame.
The whole picture is on the roof window installation page.